Machine Model: GENROE

 

Model Equations and/or Block Diagrams

Round Rotor Generator Model GENROEInduction Generator Model CIMTR1

Same as the GENROU model, except that an exponential function is used for saturation.

Parameters:

H Inertia constant, sec
D Damping factor, pu
Ra Stator resistance, pu
Xd Direct axis synchronous reactance
Xq Quadrature axis synchronous reactance
Xdp Direct axis transient reactance
Xqp Quadrature axis transient reactance
Xdpp Direct axis subtransient reactance
Xl Stator leakage reactance
Tdop Open circuit direct axis transient time constant
Tqop Quadrature axis transient time constant
Tdopp Open circuit direct axis subtransient time constant
Tqopp Quadrature axis subtransient time constant
S1 Saturation factor at 1.0 pu flux
S12 Saturation factor at 1.2 pu flux
RComp Compensating resistance for voltage control, pu
XComp Compensating reactance for voltage control, pu